Voltage |
240 VAC, Single Phase |
| Current |
15 Amps |
| Frequency |
50/60 Hz. |
| Wattage |
3600 Watts |
| Module Power Usage |
< 5 W, excluding load |
| DC Power Supply |
Internally generated, regulated and compensated |
| Physical Configuration |
Plugs in for easy interchangeability |
| Compatibility |
With industry standard control modules and main frames |
| Size & Weight |
2” W x 7” H x 7 ½” D, 1 ½ Lbs. |
Top
|
|
| Set point Range |
0 to 999° F |
| Control Accuracy |
± 1° F (0.5° C), dependent on total thermal system |
| Calibration Accuracy |
Better that 0.2 % of full scale |
|
|
|
| Thermocouple |
Type “J” grounded or ungrounded |
| External Thermocouple Resistance |
High impedance potentiometric input allows long distance
TC wiring |
| Thermocouple Isolation |
Isolated from ground & supply voltage |
| Cold Junction Compensation |
Automatic, better then 0.02 °F/ °F (0.01 °C/ °C) |
| Thermocouple Break Protection |
Automatically prohibits power to heater or thermocouple
break hold |
| Reverse Thermocouple Protection |
Automatically prohibits power to heater |
| Shorted Thermocouple Protection |
Automatically prohibits power to heater |
Top
|
|
| Output Drive |
Internal solid state triac, Zero crossing AC pulses
triggering method |
| Overload Protection |
Fuses on both sides of AC lines |
| Transient Protection |
dV/dt and transient pulse supression |
| Shorted Triac protection |
Safety relays cuts power to load |
| Power line isolation |
Optically and transformer isolated from AC lines,
Isolation voltage greater than 2500 V |
| Display |
Dual LCD displays, 7 segmented 3 digits |
| Manual Mode |
Maintains constant output power within 1% of manual set
power. Adjustable from 0 to 100% |
| Operational Modes |
- Soft Start proceeds Auto Mode
- Thermocouple break overrides Soft Start and Auto Mode
- Reversed or Shorted thermocouple overrides Soft Start and Auto
Mode
- Manual Mode overrides thermocouple break, reversed or shorted
thermocouple and Auto Mode
- Output is inhibited during all fault conditions
|
Top
|
|
| Soft Start method |
Variable stepping voltage, phase fired |
| Soft Start Duration |
5 Minutes |
| Soft Start Override temperature |
212° F |
| Anti-Arching Setting Method |
By Jumper setting |
| |
|
| Optional GBS Feature |
-
Global Alarm mode (require main frame modification)
-
Global Standby mode (require main frame modification)
-
Global Power Boost mode (require main frame
modification)
-
(For detail click on Optional GBS Features
)
|