Temperature Control Module uTC-15a Operator's Manual

[ General Description ] [ Specifications ] [ Operator's Manual ] [ Troubleshooting Guide ]

1. Standard Operating Features 3. Error Codes
2.  Selectable Features 4. Safety Summary
2a. Optional Features

Standard Operating Features

1.  Soft Start 7.   Open Triac / Open Heater
2.  Normal Operation 8.   High & Low Temperature Alarm
3.  Setting Operating Temperature 9.   Thermocouple Break Protection
4.  High Amperage Indication 10. Shorted Thermocouple Indication
5. Anti Arching 11. 100% Power
6. Shorted Triac Protection 12. Manual Operation

Soft Start : As the power is turned ON, the module will look at the existing zone temperature and determines if Soft Start cycle is needed. The Soft Start cycle is activated when zone temperature is below 212° F, at the time of  start up. The Soft Start cycle time is set at 5 min. and during this time reduced output power is applied to heater. The Soft Start time can be changed by using "rSt" option or can be locked by using "rSL" option.
Top 
Normal Operation : After completion of Soft Start cycle the control module will switch to automatic control mode. At this time the control module will apply necessary power to bring the process temperature up to the set point temperature and maintain it there.
Top 
Setting Operating Temperature : The set point is normally set at 400° F at the factory. You can change set point at any time by pressing "UP" or " DOWN" keys. The control module has been designed to remember the last entered temperature even if the module is taken out of service or lost power.
Top 
High Amperage Indication : To help protect valuable molds, cables, connectors, manifolds and other related equipment, uATC-15a control module has a safety device, which will alarm if a heater draws current above its rated capacity. The  control module allows the operator to set "HiA" value just above the heaters maximum current draw. The uATC-15a will trigger an alarm and disable the power to the heater if current draw exceeds the set value. Utilizing this feature can save time and expense by getting attention to the problem before damage occurs.
Top 
Anti-Arching : The uATC-15a module is equipped with our innovative Anti-Arching feature, that will help preventing damage to the control module and main frame in the event the module is inadvertently removed under load. This feature should not be considered a substitute for proper handling procedures, but rather a supplemental protection mechanism. 
If this module is inserted in to main frame not equipped with Anti-Arching, the system will not provide power to the heater and "toH" error code will be displayed. If this condition occurs, the Anti-Arching jumper can be moved from 2-3 (enabled) position to 1-2 (disabled) position. By repositioning the jumper to anti-arching disabled position, the module will function in main frame which are not equipped with Anti-Arching feature.
Top
Shorted Triac Protection : ITC has made provisions within the uTC-15a module for protection against shorted triac. This new circuitry disables power to the heater in the event the main triac is shorted. In a situation the power to heater is detected even when temperature is well above the set point, and module will disable power to the heater. A "tSH" error code will be displayed to avert any damage to mold or heater.
Top 
Open Triac / Open Heater : The uTC-15a will alert the operator in the event of an open triac or heater, by displaying "toH" error code. This condition is detected if the heater fails to maintain or rise to set point temperature and there is no current flowing to the heater. The time frame of this feature can be adjusted by "toh" option.
Top 
High & Low temperature Alarm : The high and low temperature alarms have been set at factory at 30° F. If the zone temperature drops 30° below or exceeds 30° the set point, the alarm will be activated.
Top 
Thermocouple Break Protection : In the event thermocouple failure is detected in operation, uTC-15a has the ability to automatically control temperature with stored Average Power Output information, if the "tcb" feature is set to "APO".
Top 
Shorted Thermocouple Indication : In the event that the control module fails to detect a rise in temperature while power is being supplied to the heaters, the uTC-15a module will activate an alarm.
Top 
100% Power Key : When "100% PWR" key is pressed and held, the module put out full power until the key is released or the process temperature reaches the high temperature alarm limit. The audible alarm will sound when this key is held to make sure that it is not done in error.
Note : The "100% PWR" key is disabled during the Soft Start cycle.
Top 
Manual Operation : To operate the control module manually, push the "MAN" key. the percentage of output power will be displayed in set point window. Push "UP" or "DOWN" keys respectively to change the output percentage. If the thermocouple feedback is available the process temperature will blink.
Note : Alarms will not operate in manual mode.
Top

Selectable Features of uTC-15a

Selectable feature changing procedure : 

  1. To enter the Option Menu, press "SEL OPTS" key the desired option code appears in the process temperature (upper) window. As you scroll through the option menu, the present setting of each option will be displayed in set point (lower) window.

  2. To change an option setting, use "UP" or "DOWN" keys.

  3. To exit the option menu, continue to press the "SEL OPTS" key until you reach the end of option menu. At this time "STR" will be displayed in the process temperature (upper) window, which indicates that your settings have been stored and the unit will resume normal operation.

Feature Code Description Factory Setting
C-F Temperature display mode, ° F or ° C ° F
AL Built in Audible Alarm, ON or OFF ON
tcb

Top

Thermocouple Break (Average Power Output). If this option is set to "APO" and thermocouple input is lost during operation, the module alarm and indicate that the thermocouple input is open. However, the instrument will continue to deliver the same average power to the heater as it had delivered just prior to losing thermocouple signal. APO
Out Select Control Algorithm Method. (F2y or Pid ) F2y (Fuzzy) will control the temperature by adjusting the amperage tot he heater, providing a ripple free effect and improved heater life. Pid (Proportional) will control the temperature by turning on and off proportionately. Typically either method will control as well as the other. However, the Pid control method must be used when the control module is operating solid state relays. F2y
rSt Soft Start Cycle (0 - 20 min.) This feature sets the amount of time that the soft start cycle is active  if a minimum temperature of 212° F has not been reached. 5 min.
utA Under Temperature Alarm (-5° to - 30° F) This feature triggers an alarm if the zone temperature falls 30° F below set point. -30° F
otA Over Temperature Alarm (+5° to +30° F) This feature activates and alarm if the zone temperature rises more than 30° F above the set point. +30° F
gfs

Top

Ground Fault Sensitivity (60 to 180 mA) This Feature allows the user to set the ground fault sensitivity value. This feature can be set to OFF, to do so set the feature to off , switch off the module and back on. 120 mA
HiA High Amperage Indication (1 to 16 Amp) If the instrument detects a current draw that exceeds the preset value, this feature will cut power to the heater and display an "HiA" warning. This feature allows for setting a current warning level just above the maximum draw of the heater. When the instrument detects a current greater than the predetermined value, it will alarm and shut off power to the heater. 15 Amp
rSL Soft Start Lock (ON or OFF) This feature prevents the Soft Start parameter from being overridden from front panel. With this feature turned on, the Soft Start cycle must be completed prior to entering either manual or automatic control mode.  ON
Pad Keypad Loackout (Locked or Unlocked) This feature locks out the front panel with exception of "SEL OPTS" key. This lockout prevents accidental changing of temperature setting etc. To lock out the front panel keys select "LOC" and to unlock the setting, select "uNL" uNL (Unlocked)
bSt Optional Feature : Global Boost (0° to 100° F) The Global Boost feature is not a standard feature, it requires modification to both the module and main frame. This feature allows for the input temperature by which the set point can be increased when Boos feature is activated. (For detail click on Optional GBS Features ) 30° F
Top

Error Codes

An Error Code flashes in the process temperature (upper) window, when an error is detected.

Error Codes Description
gFd Excess current leakage to ground in heater circuit
HiA Amperage over run. When the module detects current which is greater than the set value, it will disable power to the heater
toH The module triac or heater circuit is open. This error message will be displayed when the module detects an under temperature condition for a period longer than the value selected in "toH" and no current is detected.
tSH Main triac is shorted. This error massage displays when an over temperature condition occurs and current flow is detected. If this condition occurs, the instrument will disable power to the heater.
Top
Back to : Temperature Control Modules Index Optional GBS Features

 