Temperature Control Module uATC-15 Operator's Manual

[ General Description ] [ Specifications ] [ Operator's Manual ] [ Troubleshooting Guide ]

1. Standard Operating Features 3. Error Codes
2.  Selectable Features 4. Safety Summary
2a.  Optional Features

Standard Operating Features

1.  Normal Operation 9.  High & Low Temperature Alarm
2.  Setting Operating Temperature 10. Shorted Triac Protection
3.  Soft Start 11. Open Triac / Open Heater
4.  Ground Fault Sensitivity 12. Thermocouple Break Protection
5.  Manual Operation 13. Reversed Thermocouple Protection
6.  Amps Key 14. Shorted Thermocouple Indication
7.  Stand By Mode 15. 100% Power
8.  High Amperage Indication 16. Anti Arcing

Normal Operation : When the power switch on the module is turned ON, the control module will look at the existing zone temperature and determine if the "SOFT START" cycle is needed. The "SOFT START" cycle will be activated any time the zone temperature is below 212° F, when the module is turned ON. Upon completion of "SOFT START" cycle the control module will automatically switch to automatic control mode. At this time the control module will apply necessary power to bring the process temperature up to the set point temperature and maintain it there.
Top
Setting Operating Temperature : The set point is normally set at 400° F at the factory. You can change set point at any time by pressing "UP" or " DOWN" keys. The control module has been designed to remember the last entered temperature after being shut off until later use.
Top
Soft Start : The "SOFT START" cycle applies a reduced output power to the heater at start up. The module only activates Soft Start if the initial process temperature at the start up is below 212° F. The output is gradually increased while the zone temperature is kept below 212° F. The Soft Start cycle time is factory set at 5 min. The Soft Start time may be changed by using "rSt" option.
Top
Ground Fault Sensitivity : The uATC-15a control module is equipped with ground fault detection circuit. When Soft Start cycle terminates, the control module checks the current leakage to ground in the heater circuit. If the leakage is in excess of the value entered "gfs" option is detected,  the Soft Start cycle will be reactivated. Upon completion of second Soft Start cycle, the module will again check for leakage to ground. If the leakage is still in excess of the entered value, the control module will go into alarm & "gFd" is displayed in process temperature window. The ground fault sensitivity is factory set at 120 mA. Sensitivity may be adjusted or turned off by in option "gfs". To disable ground fault, first set the option to "OFF" then turn the module off and back on.
Top
Manual Operation : To operate the control module manually, push the "MAN" key. the percentage of output power will be displayed in the set point window. Push "UP" or "DOWN" keys to change the output percentage. If the thermocouple feedback is available the process temperature window will be blank.
Note : Alarms will not operate in manual mode.
Top
Amps Key : When "Amps" key is pressed, the process temperature (upper) window will display the average amperage draw of the heater circuit. You can read full load amps also by pressing the "100% PWR" key for several seconds while the unit is in amperage display mode. To return to process temperature press "Amps" key again.
Top
Stand-By mode : When "STBY" key is pressed the control module will automatically lower the set point to 212° F. To return back to previous set point press the "STBY" key again.
Top
High Amperage Indication : To help protect valuable molds and other related equipment, a safety device will alarm if a heater is drawing current above the rated capacity. Set the temperature in Option "HiA" to a value just above the heaters maximum draw. The uATC-15a will trigger an alarm and disable the power to the heater if current draw exceeds the set value. Utilizing this feature can save time and expense by getting attention to the problem before damage occurs.
Top
High and Low Temperature Alarm : The high and low temperature alarms have been factory set at 30° F. If the zone temperature drops 30° below the setpoint or the temperature exceeds 30° above the setpoint, the alarm will be activated. Alarm settings may be adjusted in the options "utA" or "otA". 
Top
Shorted Triac Protection : ITC has made provisions within the uATC-15a module for protection against shorted triac. Within the circuitry are relays which disables power to the heater in the event the main triac is shorted. In a situation when power to heater is detected when the temperature is well above the setpoint, and module will disable power to the heater. A "tSH" error code will be displayed to avert any damage to mold or heater.
Top
Open Triac / Open Heater : The uATC-15a will alert the operator in the event of an open triac or heater, by displaying "toH" error massage in the upper window. This condition is detected if the heater fails to maintain or rise to setpoint temperature and there is an absence of current flowing to the heater. The time frame of this feature can be adjusted in option "toh".
Top
Thermocouple Break Protection : In the event a thermocouple fails in the open condition after reaching setpoint temperature, the module will automatically control temperature with stored Average Power Output information, if the option "tcb" is set to "APO". This feature only operates at setpoint temperature.
Top
Reverse Thermocouple Protection : The module will scrutinize actual voltage through the thermocouple. In the event a negative voltage is detected, the "REV" LED will flash and power will not be applied to the heater. 
Top
Shorted Thermocouple Indication : In the event a thermocouple fails to detect a rise in temperature while power is being supplied to the heaters, the uATC-15a module will activate an alarm. The "OPEN" and "REV" LED will flash alternately.
Top
100% Power Key : When "100% PWR" key is pressed and held, the module put out full power until the key is released or the process temperature reaches the high temperature alarm limit. The audible alarm will sound when this key is held to make sure that it is not done in error.
Note : The "100% PWR" key is disabled during the Soft Start cycle.
Top
Anti-Arcing : The uATC-15a module is equipped with our innovative Anti-Arching feature, that will help preventing damage to the control module and main frame in the event the module is inadvertently removed under load. This feature should not be considered a substitute for proper handling procedures, but rather a supplemental protection mechanism. 
If this module is inserted in to main frame not equipped with Anti-Arching, the system will not provide power to the heater and "toH" error code will be displayed. If this condition occurs, the Anti-Arching jumper can be moved from 2-3 (enabled) position to 1-2 (disabled) position. By repositioning the jumper to anti-arching disabled position, the module will function in main frame which are not equipped with Anti-Arching feature.
        Note :    a)    This feature will only work with ITC's updated TC-2000 main frames.
                      b)    The Anti-Arcing feature will not prevent damage if the jumper is in disabled position.
                      c)    The Anti-Arcing feature in the module will not prevent damage if the module is used in a main frame not
                             equipped with anti-arcing.
                      d)    ITC main frame manufactured prior to March 2000 were not equipped with Anti-Arcing feature. To
                             upgrade consult factory.
Top
Selectable Features of uATC-15a

Selectable feature changing procedure : 

  1. To enter the Selectable Options Menu, press "SEL OPTS" key until the desired option code appears in the process temperature (upper) window. As you scroll through the option menu, the present setting of each option will be displayed in setpoint (lower) window.

  2. To change an option setting, use "UP" or "DOWN" keys.

  3. To exit the Selectable Options menu, continue to press the "SEL OPTS" key until you reach the end of options menu. At this time "Str" will be displayed in the process temperature (upper) window, which indicates that your settings have been stored and the unit will resume normal operation.

Feature Code Description Factory Setting
C-F Temperature display mode (° F or ° C) ° F
AL Audible Alarm (ON or OFF) ON
tcb

Top

Thermocouple Break (APO - Average Power Output). If this option is set to "APO" and thermocouple input is lost during operation, the module will alarm and indicate that the thermocouple input is open. However, instead of disabling power to heater, the instrument will continue to apply the same average power to the heater as it applied just prior to losing thermocouple signal. (APO or OFF) APO
Out Output Power Method "F2y" or "Pid".  F2y (Fuzzy) will control the zone temperature by adjusting the amperage to the heater, providing a ripple free effect and improved heater life. Pid (Proportional) will control the temperature by turning the heater on and off proportionately. Typically either method will control as well as the other. However, the Pid control method must be used when the control module is operating solid state relays.  F2y (Pid with solid state relays)
rSt Ramp Soft Start (0 - 20 min.) 5 min.
utA Under Temperature Alarm (5° to 30° F below setpoint temperature) 30° F Below setpoint temperature
otA Over Temperature Alarm (5° to 30° F above setpoint temperature) 30° F Above setpoint temperature
gFs

Top

Ground Fault Sensitivity (60 to 180 mA or OFF) To disable ground fault, first set the option to OFF, then turn the module off and then back on. 120 mA
tOH Open triac/Open heater. (0 to 255 seconds) 180 sec.
HiA High Amperage Indication (1 to 16 Amp) If the module detects a current draw that exceeds the set value, it will cut power to the heater and display an "HiA" warning. This feature allows for setting a current warning level just above the maximum draw of the heater. When the module detects a current greater than the predetermined value, it will alarm and shut off power to the heater. 15 Amp
rSL Ramp Soft Start Lock (ON or OFF) This feature prevents the Soft Start parameter from being overridden from front panel. Soft Start cycle must be completed prior to entering either manual or automatic mode. ON
PAd Keypad Loackout (LOC or uLC) This feature locks out the front panel with exception of "SEL OPTS" key. This lockout prevents accidental changing of temperature setting etc.  uLC (Unlocked)
bSt

Top

Optional Feature : Global Boost (0° to 100° F) The Global Boost feature is not a standard feature, it requires modification to both the module and the main frame. This feature allows for the input of a temperature value by which the set point can be increased when Global Boost feature is activated. (For detail click on Optional GBS Features ) 30° F

Error Codes

An Error Code flashes in the process temperature (upper) window, when an error is detected.

Error Codes Description
gFd Excess current leakage to ground in heater circuit
HiA High Amperage over run. The module detects current greater than the set value in Option "HiA" and will disable power to the heater.
toH The module triac or heater circuit is open. This module detects an under temperature condition for a time period longer than the set value selected in option "toH" and no current is detected.
tSH Main triac is shorted. This error massage displays when an over temperature condition has occured and current flow is detected. If this condition occurs, the module will disable power to the heater.
Top
Back to : Temperature Control Modules Index Optional GBS Features
 