| Problem |
Possible Solution |
| The module will not turn on. |
- Check power cord and input power.
- Is main frame turned on?
- Check fuses (ABC-15), if blown, check for wiring short.
|
| The module falsely indicates open thermocouple. |
Check thermocouple input fuses. |
| The module falsely indicates thermocouple shorted. |
Check "toH" time setting. |
| Module appears to operate properly, but no power is passing
through the heaters. |
Main frame is not set for Anti-Arching feature. Move jumper
from pin position #2 & #3 (enabled) to pi position #1 & #2
(disabled. |
| Mold is unusually cold. |
- Allow mold to warm up in Soft Start mode.
- Check mold thermocouple wiring
- Make sure input power voltage is correct
|
| Mold Overheats. |
- Is temperature display set to ° F scale?
- Check thermocouple
- Replace triac
|
| Open thermocouple. |
Check mold wiring |
| Module blows fuses. |
- Make sure heater size does not exceed module rating.
- Make sure this is not the result of a shorted heater or a short in
the mold wiring. Do not replace module until problem is corrected or
damage can result.
|
If problems are experienced with the control
module, we recommend you return it to International Temperature Control
Inc. for repair or calibration.