[ Home ] [ Product Information ] [ Contact Us ] [On Line Quotes ]


Temperature Control Module uATC-15 Specification

[ General Description ] [ Specifications ] [ Operator's Manual ] [ Troubleshooting Guide ]

Voltage

240 VAC, Single Phase
Current  15 Amps
Frequency 50/60 Hz.
Wattage 3600 Watts 
Module Power Usage < 5 W, excluding load
DC Power Supply Internally generated, regulated and compensated
Physical Configuration Plugs in for easy interchangeability
Compatibility With industry standard control modules and main frames.
Size & Weight 2” W x 7” H x 7 ½” D, 1 ½ Lbs.
Top  
Set point Range 0 to 999° F (537° C)
Control Accuracy ± 1° F (0.5° C), dependent on total thermal system
Calibration Accuracy Better that 0.2 % of full scale
   
Thermocouple Type “J” grounded or ungrounded
External Thermocouple Resistance High impedance potentiometric input allows long distance TC wiring
Thermocouple Isolation Isolated from ground & supply voltage
Cold Junction Compensation Automatic, better then 0.02 °F/ °F (0.01 °C/ °C)
Thermocouple Break Protection Automatically prohibits power to heater or thermocouple break hold
Reverse Thermocouple Protection Automatically prohibits power to heater
Shorted Thermocouple Protection Automatically prohibits power to heater
Top  
Output Drive Internal solid state triac, Zero crossing AC pulses triggering method
Overload Protection Fuses on both sides of AC lines
Transient Protection dV/dt and transient pulse suppression
Shorted Triac protection Safety relays cuts power to load
Power line isolation Optically and transformer isolated from AC lines, Isolation voltage greater than 2500 V
Display Dual LCD displays, 7 segmented 3 digits
Manual Mode Maintains constant output power within 1% of manual set power. Adjustable from 0 to 100%
Operational Modes
  • Soft Start proceeds Auto Mode
  • Thermocouple break overrides Soft Start and Auto Mode
  • Reversed or Shorted thermocouple overrides Soft Start and Auto Mode
  • Manual Mode overrides thermocouple break, reversed or shorted thermocouple and Auto Mode
  • Output is inhibited during all fault conditions
Top  
Soft Start method Variable stepping voltage, phase fired
Soft Start Duration 5 Minutes
Soft Start Override temperature 212° F
Anti-Arching Setting Method By Jumper setting
   
Optional GBS Feature
  • Global Alarm mode (require main frame modification)

  • Global Standby mode (require main frame modification)

  • Global Power Boost mode (require main frame modification)

  • (For detail click on Optional GBS Features )